A non-destructive testing (NDT) method that utilizes infrared imaging to detect thermal anomalies, ensuring early fault diagnosis and compliance with NFPA standards
Infrared (IR) thermography transforms invisible heat energy into a visible thermal spectrum, allowing maintenance teams to “see” developing failures before they cause shutdowns.
Thermal cameras do not measure temperature directly; they measure radiated energy. Emissivity ($\varepsilon$) is the measure of a material’s efficiency in radiating heat. A perfect “black body” has an emissivity of 1.0, while shiny metals (like copper busbars) may have an emissivity as low as 0.1, often leading to false “cold” readings. Technicians must adjust for emissivity to obtain accurate temperature data.
In thermography, absolute temperature is less important than relative temperature. Delta T ($\Delta T$) is the temperature difference between a target component and a reference point—usually a similar component under the same load (e.g., Phase A vs. Phase B) or the ambient air temperature. A high $\Delta T$ indicates high resistance or friction.
Heat is the primary by-product of inefficiency and failure in electrical and mechanical systems. Identifying the root cause is essential for remediation.
The most common electrical fault is a “high-resistance connection.” Loose torque, oxidation, or corrosion reduces the contact surface area, forcing current through a smaller path. This increases resistance ($R$), and since Power dissipated as heat is $I^2R$, even a slight increase in resistance generates significant localized heat (Hot Spot).
When a system is overloaded, the entire conductor heats up. However, if one phase carries significantly more current than the others (Phase Imbalance), that specific leg will appear hotter. Thermography quickly visualizes these imbalances, which often go unnoticed by standard amp-meter spot checks.
Non-linear loads (VFDs, LED lighting) create harmonic currents that can cause excessive heating, particularly in neutral conductors and transformer windings. Additionally, “inductive heating” occurs when stray magnetic fields induce currents in nearby ferrous metals (like panel enclosures), causing them to heat up even without direct electrical contact.
Thermography is versatile, covering both the power distribution network and rotating machinery.
Annual scans of Motor Control Centers (MCCs) and switchgear are vital. Common find-points include fuse clips, breaker lugs, and busbar joints. Detecting a loose fuse clip early prevents arcing faults that could destroy the entire bucket.
Friction generates heat. Misaligned shafts, under-lubricated bearings, or worn gearbox teeth create distinct thermal patterns. A “hot” motor housing might indicate internal winding insulation failure or blocked cooling vents.
In oil-filled transformers, blocked cooling fins appear “cold” (indicating no oil flow), while internal loose connections manifest as hot bushings. Thermography checks the health of the cooling system to prevent the transformer from overheating under load.
To prioritize repairs, maintenance teams rely on established standards rather than guesswork.
NFPA 70B (Standard for Electrical Equipment Maintenance) mandates that equipment be scanned annually. It requires documenting temperature differences to categorize asset health. NFPA 70E helps determine the safety boundaries (Arc Flash Boundary) required for the thermographer to open panels safely.
The InterNational Electrical Testing Association (NETA) provides a standard severity scale based on $\Delta T$ between similar components:
While NETA provides a baseline, “Criticality” must also be considered. A 5°C rise on a main service entrance breaker (critical path) is more urgent than a 20°C rise on a redundant parking lot lighting contactor.
A successful inspection requires strict adherence to operational protocols to ensure data validity and personnel safety.
You cannot find hot spots on a cold system. NFPA 70B recommends performing inspections when the system is under at least 40% of its rated load, and ideally during peak operation. Without current flow, high-resistance connections will not generate enough heat to be detected by the camera.
Thermography often requires opening hinged covers on energized equipment, exposing the thermographer to shock and arc flash hazards. Personnel must wear appropriate PPE (Arc Rated clothing, face shields, voltage-rated gloves) as dictated by the Arc Flash Risk Assessment label on the equipment.
One-off inspections are useful, but trending is powerful. By saving thermal images of the same asset year over year, teams can track the gradual degradation of a component (e.g., a bearing running 2°C hotter every month) and predict failure before it occurs.
Implementing a thermography program shifts maintenance from “Reactive” (fixing what broke) to “Predictive” (fixing what will break).
An average electrical failure causes 6 hours of downtime. Detecting a loose lug takes 5 minutes. Thermography prevents the “run-to-failure” scenario, saving thousands in lost production and emergency repair costs.
Because IR cameras operate remotely, they allow technicians to inspect high-voltage equipment from a safe distance without shutting down the process or touching live components, preserving the asset’s integrity.
Most industrial insurance carriers now require annual infrared inspections to renew policies. A certified report demonstrates due diligence, often reducing premium costs and ensuring compliance with statutory safety regulations.
Thermography is the eyes of your electrical maintenance program. By detecting invisible thermal signatures, you can identify loose connections, overloaded circuits, and mechanical wear before they escalate into catastrophic failures. Adopting routine IR inspections ensures compliance with NFPA 70B, reduces insurance risks, and protects your most valuable asset—your people.
Call to Action
Ensure your facility is compliant, safe, and resilient.
Aura Safety Risk Consultant
+91 99994 02106
Identifies arc flash hazards and defines safe working limits
Evaluates electrical risks to prevent failures and accidents
Analyzes power quality issues caused by electrical harmonics
Classifies hazardous zones for safe electrical equipment use
Assesses lightning threats and protection system needs
Optimizes relay settings for selective fault protection
Calculates fault currents to ensure system safety
Electrical safety audits and engineering solutions minimizing risks, preventing accidents.
For industrial inspections, a minimum resolution of 320 x 240 pixels is recommended. Lower resolutions (like 160 x 120) may miss small hot spots on distant components, such as overhead busway joints or substation insulators.
No. Infrared energy does not pass through solid metal or glass. To inspect components, you must open the panel door or install Infrared (IR) Windows, which are special crystal optics that allow IR transmission while keeping the panel closed and safe.
NFPA 70B now requires infrared inspections to be performed annually for most electrical equipment. Critical assets or those in harsh environments may require quarterly or semi-annual inspections.
A hot spot is generated by the component itself. A reflection is heat from a separate source (like a nearby light bulb or the thermographer’s body) bouncing off a shiny surface. Technicians distinguish them by moving the camera angle; reflections move, hot spots stay fixed.
Yes, in an energized circuit with current flowing. According to Joule’s Law ($P = I^2R$), any increase in resistance results in heat generation. If there is no load (current), there will be no heat, regardless of resistance.
Inspections should be performed by a certified Level I or Level II Thermographer who understands heat transfer physics, camera operation, and electrical safety standards (NFPA 70E)